The VR3452 circulator is used for circulation of water or a mixture of water/glycol in hot water heating systems, air conditioning systems and closed loop circulation systems. Operating modes include self-adjusting auto, proportional pressure, constant pressure, constant speed and night setback.
Specifications
- Maximum Shutoff Head: 34 feet
- Maximum Flow: 52 gpm
- Maximum Operating Pressure: 145 psi (10 bar)
- Maximum Water Temp: 230°F (110°C)
- Minimum Water Temp: 14°F (-10°C)
- Ambient Temp Range: 32°F (0°C) to 104°F (40°C)
- Minimum Inlet Pressure:
- 112˚F (50˚C) 0.73 psi / 0.05 bar
- 176˚F (80˚C) 5.8 psi / 0.4 bar
- 230˚F (110˚C) 15.95 psi / 1.1 bar
- Electrical specifications:
- 1phase,110-120V, 47-63Hz (VR3452-HY1)
- 1phase, 200-240V, 47-63Hz (VR3452-HB1)
- Operating Power: 1/4HP, 10-180W
- Rated Current:
- (1 phase, 115V) 0.1A to 2.5A
- (1 phase, 230V) 0.1A to 1.5A
- Continuous Duty
- Built-in start-up circuit
- Equipped with a cast iron casing and should be used for closed-loop systems only
- Taco circulator pumps are for indoor use only
- Acceptable for use with water or a maximum of 50% water/glycol solution
- Degree of protection: IP 44, Class 2